Square D 8911DPSG43V09 10 HP 230V 3-Phase 40A Definite Purpose Motor Starter
Square D 8911DPSG43V09 10 HP 230V 3-Phase 40A Definite Purpose Motor Starter
Couldn't load pickup availability
View full details
Product Description
Square D / Schneider Electric 8911DPSG43V09 Definite Purpose Magnetic Motor Starter
Designed for three-phase motor loads including air compressors, pumps and other definite-purpose applications. This enclosed Class 8911 DPS starter combines a 40A, 3-pole contactor with a melting-alloy overload relay and a 208–240V AC control coil.
Specifications
| Manufacturer | Square D / Schneider Electric |
|---|---|
| Part Number | 8911DPSG43V09 |
| Starter Type | Definite-purpose, non-reversing |
| Phase | Three phase |
| Contactor Rating | 40A |
| Poles | 3 |
| Motor Rating | 10 HP at 230V AC three phase; 20 HP at 460V AC three phase; 25 HP at 575V AC three phase |
| Coil / Control Voltage | 208–240V AC, 60 Hz (220V AC, 50 Hz) |
| Enclosure | NEMA Type 1 painted sheet steel |
| Overload Type | Melting-alloy thermal overload; three thermal units required and sold separately |
| Maximum System Voltage | 600V AC |
| Locked-Rotor Rating | 240A at 230V AC |
| GTIN / UPC | 785901024712 |
Air Compressor Application
Schneider Electric specifically identifies air compressors as an intended application for the Class 8911 DPS starter family. The exact 8911DPSG43V09 is a 40A enclosed three-phase starter rated by Schneider for 10 HP at 230V, making it a common configuration for 10 HP 208–230V three-phase compressor packages.
Overload Heater Selection
This 40A DPSG starter uses Square D B-series thermal units. Heater selection must be based on the motor's actual nameplate full-load current (FLA), not horsepower alone.
Recommended Heater Inserts
B-36 — 22.6–26.2A for an enclosed DPSG43 three-phase starter
B-40 — 26.3–28.0A for an enclosed DPSG43 three-phase starter
Three matching B-series thermal units are required. Verify the motor's actual nameplate FLA before ordering heaters.